Download Solution PDFFor unity power factor, the voltage regulation of a short transmission line is:
Answer (Detailed Solution Below)
Detailed Solution
Download Solution PDFVoltage regulation
Voltage regulation of a transmission line is defined as the ratio of the difference between receiving end voltage at no load and receiving end voltage at full load to the rated voltage.
The receiving end voltage at full load is considered as rated voltage.
\(VR={V_{R(no \space load)}-V_{R(full \space load)}\over V_R}\)
The sending end voltage is given by:
\(V_S=AV_R+BI_R\)
At no-load condition, IR = 0
\(V_{R(no \space laod)}={V_S\over A}\)
For a short transmission line, the parameter A = 1
\(V_{R(no \space laod)}={V_S\over 1}=V_S\)
So, the expression for voltage regulation for a short transmission line is:
\(VR={V_S-V_R\over V_R}\)
Circuit diagram of short transmission line:
For the unity power factor, the load will be purely resistive.
Hence, the current (I) and voltage (VR) across the load will be in the same phase.
From the above phasor:
\(V_S=V_R+IX_L\)
\(V_S-V_R=IX_L\)
\(VR={V_S-V_R\over V_R}\)
\(VR={IX_L\over V_R}\)
\(VR={IX_L\over IR}\)
\(VR={X_L\over R}\)
Last updated on May 9, 2025
-> PGCIL Diploma Trainee result 2025 will be released in the third week of May.
-> The PGCIL Diploma Trainee Answer key 2025 has been released on 12th April. Candidates can raise objection from 12 April to 14 April 2025.
-> The PGCIL DT Exam was conducted on 11 April 2025.
-> Candidates had applied online from 21st October 2024 to 19th November 2024.
-> A total of 666 vacancies have been released.
-> Candidates between 18 -27 years of age, with a diploma in the concerned stream are eligible.
-> Attempt PGCIL Diploma Trainee Previous Year Papers for good preparation.