Per Unit System MCQ Quiz - Objective Question with Answer for Per Unit System - Download Free PDF
Last updated on Jun 26, 2025
Latest Per Unit System MCQ Objective Questions
Per Unit System Question 1:
In the case where the voltage bases are the same, the new per unit impedance is obtained from the formula:
Answer (Detailed Solution Below)
Per Unit System Question 1 Detailed Solution
Explanation:
Per Unit Impedance Calculation
Definition: Per unit impedance is a normalized value used in power system analysis, which simplifies calculations and comparisons. It is expressed as a fraction of the base impedance of the system. When the voltage bases remain the same, the new per unit impedance can be calculated using a specific formula that adjusts the value based on the change in system base powers.
Correct Formula:
The correct formula for calculating the new per unit impedance when the voltage bases are the same is:
Option 1: \(\rm Z_{p u}^{\text {new }}=\frac{Z_{p u}^{\text {old }} S_{B}^{\text {new }}}{S_{B}^{\text {old }}}\)
This formula is derived based on the relationship between the old and new base quantities in the power system. It ensures that the impedance values are properly scaled with respect to the change in the base power values.
Explanation:
The per unit system is a convenient way of representing electrical quantities such as impedance, voltage, and current relative to a set of base values. In the case where the voltage bases remain constant, only the base power values change. The per unit impedance is scaled proportionally to the ratio of the new base power (\(S_{B}^{\text{new}}\)) to the old base power (\(S_{B}^{\text{old}}\)). This adjustment ensures consistency in calculations and comparisons across different systems.
Let’s break down the formula:
- \(Z_{p u}^{\text{old }}\): The per unit impedance value based on the old base quantities.
- \(S_{B}^{\text{new }}\): The new base power value for the system.
- \(S_{B}^{\text{old }}\): The old base power value for the system.
- \(Z_{p u}^{\text{new }}\): The per unit impedance value based on the new base quantities.
The formula effectively scales the old per unit impedance by the ratio of the new base power to the old base power. This is essential for maintaining consistency in system analysis when the base power values are updated.
Advantages of Using Per Unit System:
- Simplifies power system calculations by normalizing values.
- Facilitates comparison between different system components.
- Eliminates the need for unit conversions during calculations.
- Provides a clear representation of electrical quantities relative to the system base values.
Important Information
To further understand the analysis, let’s evaluate the other options:
Option 2: \(\rm Z_{p u}^{\text {old }}=\frac{Z_{p u}^{\text {new }} S_{B}^{\text {new }}}{S_{B}^{\text {old }}}\)
This formula is incorrect because it reverses the relationship between the old and new per unit impedance values. Instead of scaling the old impedance to obtain the new impedance, it attempts to derive the old impedance from the new impedance. While mathematically possible, this is not the standard approach used in power system analysis.
Option 3: \(\rm Z_{p u}^{\text {new }}=\frac{Z_{p u}^{\text {old }} S_{B}^{\text {old }}}{S_{B}^{\text {new }}}\)
This formula is incorrect as it inversely scales the old per unit impedance with respect to the ratio of the base power values. It would result in an incorrect representation of the new per unit impedance, leading to errors in system analysis.
Option 4: \(\rm Z_{p u}^{\text {new }}=\frac{Z_{p u}^{\text {old }} S_{B}^{\text {new }} V_{B}^{\text {old }}}{S_{B}^{\text {old }} V_{B}^{\text {new }}}\)
This formula introduces voltage base values (\(V_{B}^{\text{old}}\) and \(V_{B}^{\text{new}}\)) into the calculation, which is unnecessary when the voltage bases are the same. When the voltage bases do not change, these terms cancel out, and the formula simplifies to Option 1. Including voltage base values in this case complicates the calculation unnecessarily.
Conclusion:
The correct formula for calculating the new per unit impedance when the voltage bases remain constant is Option 1. This formula ensures proper scaling of the old per unit impedance value based on the ratio of the new base power to the old base power. It is essential for consistent and accurate power system analysis, especially when transitioning between different base quantities.
Per Unit System Question 2:
The per unit impedance of a circuit element is 0.30. If the base kV and base MVA are halved, then the new value of the per unit impedance of the circuit element will be:
Answer (Detailed Solution Below)
Per Unit System Question 2 Detailed Solution
Explanation:
Per Unit Impedance in Power Systems
Definition: The per unit (p.u.) system is a method used in power systems to normalize system quantities (impedance, voltage, current, power) to a common base. It simplifies calculations and comparisons by expressing system values as fractions or multiples of base values. The per unit impedance is given by the formula:
Zpu = Zactual × (Base MVA / Base Voltage²)
Where:
- Zactual = Actual impedance in ohms.
- Base MVA = Power base in MVA.
- Base Voltage = Voltage base in kV.
Given Data:
- Initial per unit impedance (Zpu, initial): 0.30
- Base kV and Base MVA are halved.
We need to calculate the new per unit impedance (Zpu, new) after the base values are halved.
Step-by-Step Solution:
Step 1: Relationship between per unit impedance and base values
The per unit impedance is inversely proportional to the square of the base voltage and directly proportional to the base MVA. Mathematically:
Zpu ∝ Base MVA / (Base Voltage)²
Let the initial base values be:
- Base MVA = Sbase, initial
- Base Voltage = Vbase, initial
And the new base values after halving are:
- Base MVA = Sbase, new = Sbase, initial / 2
- Base Voltage = Vbase, new = Vbase, initial / 2
Step 2: Express the new per unit impedance in terms of the initial impedance
The ratio of the new per unit impedance to the initial per unit impedance is given by:
Zpu, new / Zpu, initial = (Sbase, new / Sbase, initial) × (Vbase, initial² / Vbase, new²)
Substitute the new base values:
- Sbase, new = Sbase, initial / 2
- Vbase, new = Vbase, initial / 2
Zpu, new / Zpu, initial = [(Sbase, initial / 2) / Sbase, initial] × [Vbase, initial² / (Vbase, initial / 2)²]
Simplify the terms:
Zpu, new / Zpu, initial = (1 / 2) × (Vbase, initial² / [Vbase, initial² / 4])
Zpu, new / Zpu, initial = (1 / 2) × 4
Zpu, new / Zpu, initial = 2
Therefore:
Zpu, new = 2 × Zpu, initial
Step 3: Calculate the new per unit impedance
Substitute the given initial per unit impedance (Zpu, initial = 0.30):
Zpu, new = 2 × 0.30 = 0.60
Thus, the new per unit impedance is 0.60.
Correct Option: Option 2 (0.6)
Additional Information
To further understand the analysis, let’s evaluate the incorrect options:
Option 1: 0.3
This option assumes that the per unit impedance remains unchanged even after the base values are altered. However, per unit impedance is dependent on the base values, as shown in the formula. When the base kV and base MVA are halved, the per unit impedance changes accordingly. Therefore, this option is incorrect.
Option 3: 0.003
This option represents a drastic reduction in the per unit impedance, which is not possible given the relationship between base values and per unit impedance. Halving the base MVA and base kV results in a doubling of the per unit impedance, not a reduction to such a small value. Hence, this option is incorrect.
Option 4: 0.006
Similar to option 3, this value is unrealistically small and does not align with the mathematical relationship between per unit impedance and the base values. The correct calculation shows that the per unit impedance doubles, not decreases. Thus, this option is also incorrect.
Option 5: (No option provided)
Since no value is specified for this option, it cannot be considered as a valid choice.
Conclusion:
The correct answer is Option 2 (0.6). When the base kV and base MVA are halved, the per unit impedance doubles, as derived using the formula for per unit impedance and its dependence on base values. Understanding the relationship between system quantities and base values in the per unit system is crucial for analyzing and simplifying power system calculations.
Per Unit System Question 3:
The per unit value of any quantity is defined as:
Answer (Detailed Solution Below)
Per Unit System Question 3 Detailed Solution
The per unit value of any quantity is defined as the ratio of the actual value of that quantity to its base value, both measured in the same unit. Mathematically, it can be expressed as:
his definition allows for a standardized comparison of quantities by normalizing them to a common reference, which is particularly useful in fields such as electrical engineering and economics.
Per Unit System Question 4:
The impedance per phase of a 3-phase transmission line on a base of 1000 MVA 100 kV is 2 pu. The value of this impedance on a base of 4000 MVA and 400 kV would be
Answer (Detailed Solution Below)
Per Unit System Question 4 Detailed Solution
Concept:
Per unit quantity:
Per unit quantity = Actual quantity in the units / Base (or) reference quantity in the same units
⇒ Per unit impedance Zpu = Zactual / Zbase
⇒ Zpu = ZΩ × MVAb / (kVb)2
Conversion of one per unit impedance into another per unit impedance is given by
Calculation:
Given that
Zpu old = 2 pu
MVAold = 1000 MVA
kVb old = 100 kV
MVAnew = 4000 MVA
kVb new = 400 kV
Important PointsNOTE: The official answer key was given as option 3 with 100 MVA as old MVA. But it gives 5pu as answer which is not possible as pu value is always less than 1. So we have modified the old MVA value as 1000 MVA in the Question, then we could successfully get the desired & conceptually correct answer.
Per Unit System Question 5:
The per unit impedance of a line is X p.u. If base voltage is tripled and base MVA is doubled, the new per unit impedance is:
Answer (Detailed Solution Below)
Per Unit System Question 5 Detailed Solution
Concept:
Per unit quantity:
Per unit quantity = Actual quantity in the units / Base (or) reference quantity in the same units
⇒ Per unit impedance Zpu = Zactual / Zbase
⇒ Zpu = ZΩ × MVAb / (kVb)2
Conversion of one per unit impedance into another per unit impedance is given by
Calculation:
Let's consider
Zpu old = x
MVAold = M
kVb old = V
As base kV and base MVA are both doubled
MVAnew = 2M
kVb new = 3V
⇒ Xpu(new) = x × (2M / M) × (V / 3V)2 = x/9
=
Top Per Unit System MCQ Objective Questions
A 4 kVA, 400/200 V single-phase transformer has resistance of 0.02 pu and reactance of 0.06 pu. Its actual resistance and reactance referred to HV side, are respectively
Answer (Detailed Solution Below)
Per Unit System Question 6 Detailed Solution
Download Solution PDFConcept:
The relation between new per-unit value & old per unit value impedance
Also
Where,
Zbase = Base value of impedance
ZActual = Actual value of impedance
(Zpu)new = New per unit value of impedance
(Zpu)old = Old per unit value of impedance
kVbase = Old base value of voltage
kVnew = New base value of voltage
MVAnew = New base value of power
MVAold = Old base value of power
Additional Information
Turns ratio for the transformer is given by
Where,
Vp is the voltage on the primary side
Vs is the voltage on the secondary side
Ip is current on the primary side
Is is current on the secondary side
Np is the number of turns on the primary side
Ns is the number of turns on the secondary side
In the transformer, if
Then the value of the equivalent resistance referred to the secondary side is
∴
Similarly, if
Then the value of the equivalent reactance referred to the secondary side is
∴
Calculation:
Base impedance
Resistance in ohm to HV side =
Reactance in ohm to HV side =
The per unit impedance of a transformer is:
Answer (Detailed Solution Below)
Per Unit System Question 7 Detailed Solution
Download Solution PDFPer unit system:
It is usual to express voltage, current, voltamperes and impedance of an electrical circuit in per unit (or percentage) of base or reference values of these quantities.
The Per Unit value of any quantity is defined as
PU value = actual value/base value
Per unit system in transformers:
The per unit impedance of a transformer is the same whether computed from primary or secondary side so long as the voltage bases on the two sides are in the ratio of transformation (equivalent per phase ratio of a three-phase transformer which is the same as the ratio of line-to-line voltage rating).
Transformation ratio of transformer is given by K = V2/V1 = E2/E1 = N2/N1.
Where N1 is the number of primary turns
V1 is the primary voltage
N2 is the number of secondary turns
V2 is the secondary voltage
The per unit impedance of a synchronous machine is 0.242. If base voltage is increased to 1.1 times, then per unit value will be:
Answer (Detailed Solution Below)
Per Unit System Question 8 Detailed Solution
Download Solution PDFConcept:
The relation between new per-unit value & old per unit value impedance
Also
Where,
(Zpu)new = New per unit value of impedance
(Zpu)old = Old per unit value of impedance
kVbase = Old base value of voltage
kVnew = New base value of voltage
MVAnew = New base value of power
MVAold = Old base value of power
Calculation:
When the voltage bases is increased to 1.1 times (i.e. kVnew = 1.1kVbase), the new per unit impedance is
The per unit impedance Z(Pu) in 3 - phase system is -
Answer (Detailed Solution Below)
Per Unit System Question 9 Detailed Solution
Download Solution PDFConcept:
Per unit quantity:
Per unit quantity = Actual quantity in the units / Base (or) reference quantity in the same units
⇒ Per unit impedance Zpu = Zactual / Zbase
⇒ Zpu = ZΩ × MVAb / (kVb)2
Conversion of one per unit impedance into another per unit impedance is given by
A synchronous generator is rated at 40 MVA, 10 kV and 50 Hz. The base impedance of the generator will be:
Answer (Detailed Solution Below)
Per Unit System Question 10 Detailed Solution
Download Solution PDFThe correct answer is option 4):(2.5 Ω)
Concept:
For an AC network,
VA Rating =
Where V is voltage in volt
Z is the impedance (base) in Ω
Calculation:
VA rating = 40 MVA = 40 × 106 VA
V = 10 × 103 volts
=
Calculate the per-unit synchronous reactance on the base value of 200 MVA and 20 kV when a 100 MVA with 20 kV synchronous generator has 1pu synchronous reactance.
Answer (Detailed Solution Below)
Per Unit System Question 11 Detailed Solution
Download Solution PDFConcept:The relation between new per-unit value & old per unit value of reactance
Also
Where,
(Xpu)new = New per unit value of reactance
(Xpu)old = Old per unit value of reactance
kVbase = Old base value of voltage
kVnew = New base value of voltage
MVAnew = New base value of power
MVAold = Old base value of power
Calculation:
Given that,
Xd(old) = 1 pu
MVA(new) = 200
MVA(old) = 100
kV(old) = 20
kV(new) = 20
∴
Which of the following depicts Per-unit value of a quantity?
Answer (Detailed Solution Below)
Per Unit System Question 12 Detailed Solution
Download Solution PDFPer unit (p.u.) quantity:
The per-unit value of any quantity is defined as the ratio of actual value in any unit to the base or reference value in the same unit.
The per-unit value is dimensionless.
Per unit impedance (Zpu):
Zpu is defined as the ratio of actual value to base impedance.
It is also defined as The ratio of full-load volt-amperes to short-circuit volt-amperes.
Za = Actual impedance
ZB = Base impedance
(kVA)B = Base kVA
(kV)B = Base voltage in kV
Important points:
- Per unit voltage (Vpu) = (kV)actual / (kV)B
- Short circuit current in pu = Actual current / Base current
The relation between the old and new per unit impedance values is given by:
Answer (Detailed Solution Below)
Per Unit System Question 13 Detailed Solution
Download Solution PDFThe relation between new per-unit value & old per unit value impedance
Also
Where,
(Zpu)new = New per unit value of impedance
(Zpu)old = Old per unit value of impedance
kVbase = Old base value of voltage
kVnew = New base value of voltage
MVAnew = New base value of power
MVAold = Old base value of power
Write the expression to calculate p.u. impedance. Let Vb, be the base voltage, Z is the Actual impedance and kVAb be the base kilovolt amperes.
Answer (Detailed Solution Below)
Per Unit System Question 14 Detailed Solution
Download Solution PDFPer Unit System:
The per-unit value of any quantity is defined as the ratio of actual value in any unit to the base or reference value in the same unit.
Any quantity is converted into per unit quantity by dividing the numeral value by the chosen base value of the same dimension. The per-unit value is dimensionless.
PU Value (PU) =
Here, A is the actual value in any unit
B is the Base or reference value in the same unit
Consider the base value of voltage is (kVB), the Base value of current is (IB) and the base value of apparent power is (kVAB)
And, Base value of current (IB) =
Now, the Base value of the impedance (ZB) will be the ratio of the base value of voltage to the current.
⇒ ZB =
From equation (1),
ZB =
Hence, per unit value of impedance can be written as if Z is the actual value of impedance,
ZPU (1000) =
Since the above expression is given infraction of 1000 units,
Hence per unit value will be given as,
ZPU =
The percentage reactance of a circuit is defined as
Answer (Detailed Solution Below)
Per Unit System Question 15 Detailed Solution
Download Solution PDFThe percentage reactance of a circuit is defined as the percentage of the total phase voltage dropped in the circuit when full-load current is flowing through it.
% X =
where, X = Reactance in ohms per phase
I = Full load current
V = Phase Voltage